buckofdurham said:

The poco's point of attachment to the house. Can this be above the weather head at all? . .

Click to expand...
230.54(C) Service Heads and Goosenecks Above Service-Drop Attachment. Service heads and goosenecks in service-entrance cables shall be located above the point of attachment of the service-drop conductors to the building or other structure.


Exception: Where it is impracticable to locate the service head or gooseneck above the point of attachment,

the service head

or gooseneck

location shall be permitted not farther

than 600 mm (

24 in.) from the point of attachment.


You are also required to meet the serving electric utility's service requirements.

Service heads and goosenecks in service-entrance cables shall be located above the point of attachment of the service-drop conductors to the building or other structure.You are also required to meet the serving electric utility's service requirements.

The point of attachment of the overhead service conductors to a building or other structure shall provide the minimum clearances as specified in 230.9 and 230.24 . In no case shall this point of attachment be less than 3.0 m (10 ft) above finished grade.